Click&Go User’s Manual Examples and Applications
4-26
Programming Manners
1. Lights should be turned ON locally (for the motion sensor) and remotely
2. Report the current relay counts via e-mail upon reaching 1,000 uses
3. After a relay is replaced, site maintainers can manually reset the counts by pressing the
RESET button
Click&Go Rule-set
NOTE
Internal Register-0 in this case is used to control the relay output to a light. The control is done
outside the ioLogik or locally depending on the DI status when running Click&Go logic. Refer to
the appendix for the Modbus/TCP Address table of the internal registers.