Moxa MGATE EIP3270I Manuel d'utilisateur Page 21

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 48
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 20
MGate EIP3000 Series Users Manual Hardware: EIP3270, EIP3270I
Jumpers
SW 2 SW 1
The DIP switches are located beneath the DIP switch panel on the side of the unit.
To add a 120 termination resistor, set switch 3 on the port’s assigned DIP switch to ON; set
switch 3 to OFF (the default setting) to disable the termination resistor.
To set the pull high/low resistors to 150 K, set switches 1 and 2 on the port’s assigned DIP switch
to OFF. This is the default setting.
To set the pull high/low resistors to 1 K, set switches 1 and 2 on the port’s assigned DIP switch to
ON.
Switch 4 on the port’s assigned DIP switch is reserved.
ATTENTION
Do not use the 1 K pull high/low setting on the MGate EIP3000 when using the RS-232 interface.
Doing so will degrade the RS-232 signals and reduce the effective communication distance.
4-4
Vue de la page 20
1 2 ... 16 17 18 19 20 21 22 23 24 25 26 ... 47 48

Commentaires sur ces manuels

Pas de commentaire