ioLogik Cellular Micro RTU Controller Click&Go Logic
4-27
Repeat interval N/A Timer = N sec”
“THEN” action
triggered
THEN/ELSE Actions
Under the THEN column, you can specify up to 3 actions that will be performed when the IF conditions are
satisfied. 3 actions under the ELSE column will also be performed when the IF is NOT satisfied. Possible
actions include changing the status of a DO channel, starting or stopping an Event Counter, or sending a
message by SNMP trap, TCP, UDP, or e-mail.
If Conditions
Result of
AND Logic
Trigger of
Then Actions
Trigger of
ELSE Actions
A1 A2 A3
0 0 0 0 NO YES
0 0 1 0 NO YES
0 1 0 0 NO YES
0
1
1
0
NO
YES
1 0 0 0 NO YES
1 0 1 0 NO YES
1 1 0 0 NO YES
1 1 1 1 YES YES
If Conditions
Result of
OR Logic
Trigger of
Then Actions
Trigger of
ELSE Actions
A1 A2 A3
0 0 0 0 NO YES
0 0 1 1 YES NO
0
1
0
1
YES
NO
0 1 1 1 YES NO
1 0 0 1 YES NO
1 0 1 1 YES NO
1 1 0 1 YES NO
1
1
1
1
YES
NO
THEN/ELSE actions can be specified as follows:
THEN/ELSE
Actions
Operators Remark
Counter RESET Counter-x represents the number of the
Event Counter channel
DO ON, OFF DO-x represents the number of the channel.
Pulse Output STOP, START Pulse Output-x represents the number of the channel
AO Built-in or Expansion
Relay RESET ResetCNT-x represents the number of the relay channel.
Internal
Register
Reg-x represents the number of the internal register.
x = 00 to 23 / Trigger Value: 0 to 255