Vue de la page 91
ioLogik Cellular Micro RTU Controller Click&Go Logic
4-19
IF “A” THEN “B”, ELSE “C”
For one control logic rule, there are three “A’s” that can be configured. “A” refers to the IF conditions that
trigger an action. These three conditions can be operated by ANDor ORlogic. If “AND” logic is used, all
three conditions must be true to create a positive result. If ORlogic is used, one or more true conditions must
be met to trigger the action.
A1 A2 A3
Result of
AND Logic
A1 A2
A3
Result of
OR Logic
0 0 0 0 0 0 0 0
0 0 1 0 0 0 1 1
0 1 0 0 0 1 0 1
0 1 1 0 0 1 1 1
1 0 0 1 1 0 0 1
1 0 1 1 1 0 1 1
1 1 0 1 0 0 0 1
1 1 1 1 1 1 1 1
The 24 rules are defined individually and are executed one by one in a loop. The 2
nd
rule can only be processed
after running the 1
st
rule, and the entire rule-set will start running from the beginning after the last rule is
processed.
You will see a list of the rules in the current rule-set on the main screen. Double Click on a rule to open that
rule’s configuration window, as shown in the following figure, or double click on an empty rule to start a new
rule.
Under Relation between conditions, select AND to specify that all conditions must be satisfied for the
actions to take place; select OR to specify that any one of the conditions can be satisfied for the actions to take
place. The Equivalent Logic Statement at the bottom shows a real-time text-based summary of the rule that
you are defining. It provides a useful way to make sure the rule is designed as you intended.